4.4.3.23.6設(shè)計(jì)要求
投標(biāo)人應(yīng)當(dāng)對(duì)壁板、屋頂和內(nèi)墻的荷載設(shè)計(jì)負(fù)全責(zé),應(yīng)當(dāng)使其能夠承載不高于美國(guó)國(guó)家標(biāo)準(zhǔn)組織所制定標(biāo)準(zhǔn)的每單位最大允許應(yīng)力,并且不超過(guò)下文段落所提到的最大允許偏位。所有隔熱的壁板中都應(yīng)當(dāng)使用次檁條,嵌板應(yīng)當(dāng)能夠銜接兩個(gè)或者兩個(gè)以上的檁條的跨度。
投標(biāo)人應(yīng)當(dāng)任用合格的工程師實(shí)施或者監(jiān)督設(shè)計(jì)工作。
用于壁板、屋頂以及內(nèi)墻的各個(gè)組件之間的連結(jié)、組件與檁條之間的連結(jié)、以及組件與其他部件之間的連結(jié)的扣件,在不超過(guò)可容許的最大應(yīng)力情況下,也應(yīng)當(dāng)能夠承載一定的重量。
無(wú)論是隔熱的還是非隔熱的壁板、屋頂以及內(nèi)墻,就其通常的平面而言,其負(fù)載的最大可容許的偏位是,兩個(gè)檁條之間的凈跨的承載應(yīng)當(dāng)不超過(guò)設(shè)計(jì)載重的1/180。
建筑物的風(fēng)荷載應(yīng)當(dāng)完全負(fù)荷美國(guó)國(guó)家標(biāo)準(zhǔn)局所制定的A58.1荷載標(biāo)準(zhǔn)規(guī)定,其風(fēng)荷載是基于120千米/小時(shí) 的風(fēng)速而言,其最小活荷載應(yīng)當(dāng)不低于100千克/平方米。
對(duì)金屬板來(lái)說(shuō),其最大的纖維應(yīng)力應(yīng)當(dāng)不超過(guò)前述的14千克/平方米的這個(gè)誤差。
散熱需求:
對(duì)于隔熱壁板、屋頂和內(nèi)墻來(lái)說(shuō),其整體散熱系數(shù)U在靜止空氣中應(yīng)當(dāng)不超過(guò)0.75瓦/平方米•攝氏度。
若業(yè)主要求,投標(biāo)人應(yīng)當(dāng)將其測(cè)試結(jié)果提交給業(yè)主,以證明其所用材料的散熱性能。
隔音要求:
如果要求有隔音措施,那么其應(yīng)當(dāng)有一個(gè)隔音系數(shù)(NRC),根據(jù)美國(guó)材料試驗(yàn)協(xié)會(huì)(ASTM)制定的C423標(biāo)準(zhǔn),該系數(shù)應(yīng)當(dāng)不低于0.85。若業(yè)主要求,投標(biāo)人應(yīng)當(dāng)將相關(guān)測(cè)試結(jié)果提交給業(yè)主,以證明其所用材料的隔音性能。
耐候性要求:
所有壁板和屋頂在完成后應(yīng)當(dāng)是防風(fēng)、防雨、防塵的。
在設(shè)計(jì)隔熱壁板時(shí),應(yīng)當(dāng)采取預(yù)防措施使這些都能夠排出表面,避免它們?cè)诟鱾(gè)組裝層之間沉積。
4.4.3.23.7 儲(chǔ)存
所有壁板材料、組件、扣件、以及其他零件應(yīng)當(dāng)離地儲(chǔ)存,將其遮蔽,置于干燥、適合其存放的環(huán)境中。
投標(biāo)人應(yīng)當(dāng)將與業(yè)主一道安排未使用的材料的臨時(shí)存儲(chǔ)點(diǎn),并且有責(zé)任適當(dāng)?shù)拇娣、保管這些材料以防止其損壞、消耗等。材料的所有保管費(fèi)用已經(jīng)包含在合同價(jià)格中。
4.4.3.23.8 材料與設(shè)計(jì)(細(xì)節(jié)?)
金屬板
金屬薄板應(yīng)當(dāng)是鋼板的,且能夠與裝修后的整體兼容。冷軋鋼板應(yīng)當(dāng)滿足美國(guó)材料試驗(yàn)協(xié)會(huì)(ASTM)所制定的A446,B級(jí) G90“鍍鋅薄鋼板”的標(biāo)準(zhǔn)。歐洲規(guī)范EN10142號(hào)標(biāo)準(zhǔn):1990,EN10147號(hào)標(biāo)準(zhǔn):1992電鍍鋅275克/平方米。根據(jù)EN10142:1990的兩面三點(diǎn)測(cè)試。
金屬的厚度應(yīng)當(dāng)符合以下要求:
a)金屬厚度應(yīng)當(dāng)根據(jù)負(fù)載要求決定,但是應(yīng)當(dāng)不少于根據(jù)下表的扁梁寬度得到的相應(yīng)的厚度。珠緣可能被歸入平面以減少扁梁寬度。
3英寸扁梁 4英寸扁梁 6 英寸扁梁
美國(guó)標(biāo)準(zhǔn)平均值22 美國(guó)標(biāo)準(zhǔn)平均值20 美國(guó)標(biāo)準(zhǔn)平均值18
b)無(wú)論負(fù)載和凈跨如何,只要鋼板是按照負(fù)載和凈跨要求焊接的,其厚度最小是0.72毫米額定TCT,最大為0.85毫米TCT。
金屬板飾面
壁板、屋頂、貼面、遮雨板、排水溝的中用到的飾面應(yīng)當(dāng)是下面所提到的幾種涂層中選擇,螺旋形是首選形狀,然后再根據(jù)“涂層測(cè)試”的相關(guān)要求進(jìn)行改變。
飾面涂層由聚偏二氟乙烯加、雙面兩層的聚偏氟乙烯作為屋頂與壁板內(nèi)外雙面的底漆,無(wú)論該屋頂和壁板是否隔熱。
“聚偏二氟乙烯”作為頂漆材料,是將一種雙層的“Kynar認(rèn)證的聚偏二氟乙烯”材料,其含有80%或者80/2比例的氟碳化合物(聚偏氟乙烯),應(yīng)用于根據(jù)金屬壁板的規(guī)格要求所制造的特定的鋼板的面上,以及與前述所提到的鋼板的要求相同的屋頂材料上。
干膜的總厚度為48微米,包括防腐蝕的環(huán)氧樹(shù)脂的底漆和Kynar500認(rèn)證的聚偏二氟乙烯頂漆。
背面的顏色應(yīng)當(dāng)是淺灰色,或者是標(biāo)準(zhǔn)的制造商提供的淺灰。鋼材最終的涂層顏色應(yīng)當(dāng)交由雇主或者業(yè)主進(jìn)行確定。
隔音處理
對(duì)隔熱的壁板、屋頂需要進(jìn)行隔音處理,在中間的芯板上鑿滿直徑3.00毫米,以五毫米三角形為間距排列的孔,以此來(lái)達(dá)到前述的不低于0.85的NRC值的標(biāo)準(zhǔn)。
隔熱
隔熱的壁板或者屋頂(外墻和電氣室)應(yīng)當(dāng)達(dá)到如下隔熱標(biāo)準(zhǔn):
材料:最小密度為60千克/立方米的纖維玻璃、礦石或者熔渣。
頂部隔熱應(yīng)當(dāng)完全由150微米厚的聚乙烯保護(hù)層密封。
隔熱層的厚度:若無(wú)特別說(shuō)明,則至少為3.75厘米。
4.4.3.23.6 DESIGN REQUIREMENTS
STRUCTURAL REQUIREMENTS
The Bidder shall be fully responsible for the design of siding, roofs and interior walls to withstand the specified loads, without exceeding the maximum allowable unit stresses according to AISI, and without exceeding the allowable deflections as specified in paragraph below. Subgirts shall be used for all insulated siding. Panels may be designed as continuous over two or more spans, according to the girt or purlin spacings covered.
The Bidder shall have qualified engineers to perform or supervise the design work.
Fasteners for attaching siding, roof and interior wall component to each other and to grits and other structural supports shall be designed to withstand the specified loads without exceeding maximum allowable unit stresses for such fasteners.
The Maximum allowable deflection for insulated or uninsulated siding, roofs or interior walls subjected to the design loads shall not exceed 1/180 of the clear span between grits or purlins, in the direction normal to the plane of the siding, roof or interior wall.
Design wind loads shall conform to all applicable requirement of ANSI A58.1, with wind loads based on a basic wind speed of 120 km/hr, and the minimum design live load for the roof deck shall be 100 kg/m2.
The maximum fibre stress shall not exceed for the foregoing specified deflection 14 kg/m2 for steel panels.
THERMAL REQUIREMENTS
The overall coefficient of thermal transmission U for insulated siding, roofs and interior walls shall not exceed 0.75 watt/m2 °C in still air.
Test data shall be submitted to Owner if requested to substantiate Bidders claims as to the thermal properties of his materials used for construction.
ACOUSTIC REQUIREMENTS
If acoustically treated areas are required, they shall have a Noise Reduction Coefficient (NRC), in conformance with ASTM C423, of not
0310287
Revision 0 Part 4.4-260 PLTU Adipala (PLTU 2 Jawa Tengah)
1 x (600-700 MW) Location Cilacap
BOOK III
PART 4.4 Civil Works 4.4.3 Technical Specification
less than 0.85 and the Bidder shall submit a test report to the Owner if requested to support his claims for the NRC value of his materials used for construction.
WEATHERTIGHTNESS
All completed siding and roofs shall be weather watertight and dust tight.
Provision shall be made, in the design of insulated siding to drain to the exterior of siding of any condensation forming within the assemblies.
4.4.3.23.7 STORAGE
All siding materials, components, fasteners and other accessories shall be stored dry, off the ground and under protective cover, in a satisfactory manner.
The Bidder shall arrange with the Owner for temporary storage of materials not erected, and shall be responsible for storing these materials in such a manner as to preclude damage, deterioration, etc. All costs for such protection shall be included in the Contract Price.
4.4.3.23.8 MATERIALS AND DETAILS
METAL SHEETS
Metal sheets shall be of steel and be compatible with the coat finish system. Cold rolled steel sheets of structural quality shall confirm to the requirement of ASTM A446, Grade B, G 90 "Zinc Coated Steel Sheets". European Norm EN 10142 : 1990, EN. 10147: 1992 with galvanize Z 275 gr/m2. Two side at three point test accprding to EN 10142: 1990.
The metal thickness shall comply with one of the following requirements.
a) Metal thickness shall be determined from the defined loading
requirements, but shall be not less than that determined from the
width-of-flat surface in accordance with the following table. Beads
may be incorporated into flat surface to reduce the width-of-flat.
3-inch flat 4-inch flat 6-inch flat
USStd. 22'ga US Std. 20 ga US Std. 18 ga
b) The thickness shall be minimum 0.72 mm nominal thickness (TCT)
up to maximum 0.85 mm TCT regardless of loading and span when
sheets are fluted as required for loading and span.
0310288
Revision 0 Part 4.4 - 261 PLTU Adipala (PLTU 2 Jawa Tengah)
1 x (600-700 MW) Location Cilacap
BOOK ill
PART 4.4 Civil Works 4.4.3 Technical Specification
METAL SHEET FINISHES
Finish of siding, roofing, trim, flashing and gutter shall be one of the following specified coatings, coil coated on the sheets metal prior to forming, and modified as necessary to comply with the requirements defined in section "Coating Test".
Finish coating shall comprise of PVF2 Plus, a double-two layer polyvinylidene fluoride applied on primer for both exterior and interior surface on insulated or uninsulated roof and wall panels.
The "PVF2 Plus" acting as top coat, is a double coated "PVF2 Kynar 500", a 80 % or 80/20 fluorocarbon (polyvinylidene fluoride) applied to the special steel substrate in accordance with the requirements of the metal siding and roofing fabricator but conform with the metal sheet requirement as stipulated on previous section.
Total dry film thikness of min. 46 microns composed of both an epoxy corrosion inhibitive premier and the top coat PVF2 plus Kynar 500.
The color of reverse side shall be light gray or standard manufacturer's light gray. The final colour coat of steel cladding shall be submitted to the employer / owner for approval.
Acoustic Treatment
Where an acoustic treatment is required for insulated siding, or roofing, the interior sheet shall be fully perforated with 3.0 mm diameter holes and 5 mm triangle spacing that will provide NRC value of not less than 0.85 as specified in Clause mentioned before.
INSULATION
Where insulated siding & roof (external wall & electrical room) is indicated, the insulation shall conform to the following requirements:
Material: shall be fibrous glass, rock or slag with minimum density of 60 kg/m3.
The roof insulation shall be reinforced on down face with vinyl or aluminum foil. The thickness of vinyl shall not be less than 0.01 mm and the thickness of aluminum shall not be less than 0.0025 mm.
The wall insulation shall be completely enclosed with minimum 150-micron thick polyethylene protective cover.
Thickness of insulation: shall be a minimum of 3.75 cm if not otherwise stated.